Detail AEMC Multi-Function Installation Tester Model C.A 6117 Aemc

Alat Laboratorium Mikrobiologi

Deskripsi produk
Multi-Function Installation Tester Model C.A 6117
The High performance C.A6117 offers excellent measurement stability, even in electrically noisy industrial environments. All the measurements needed to test an electrical installation are available: continuity, resistance, insulation, ground resistance, selective earth measurements, loop impedance and type A and AC RCDs (GFCI circuits). The 6117 can also be used to measure voltage, frequency, AC current (via a current clamp), active power, harmonics and phase rotation.

The C.A6117 is also equipped with type B RCD testing, a built in fuse table and a voltage drop feature.
Specificactions:

CONTINUITY / RESISTANCE
I Rated / Range / Resolution
I > 200mA / 39.99Ω/ 0.01Ω / ± (1.5% of R + 2cts)
12mA / 39.99Ω & 399.9Ω / 0.01 & 0.1Ω /± (1.5% of R + 5cts) with beep
Range / Resolution / Accuracy
4 kΩ/ 1Ω / ±(1.5% of R + 5cts) 40 kΩ - 400 kΩ/ 10Ω - 100Ω / ±(1.5% of R + 2cts)
INSULATION
Rated Voltage
Utest: 50 /100 / 250 / 500 / 1000VDC
Range / Resolution / Accuracy
0.01MΩ to 2GΩ / 10kΩ to 1MΩ / ±(5% of R + 3cts)
Short Circuit Current
≤ 3mA
GROUND
3P GROUND
Range / Resolution / Accuracy
0.50 to 40Ω/ 0.01Ω / ±(2% of R + 10cts) 40Ω to 15kΩ / 0.1 to 1Ω / ±(2% of R + 2cts)
15 to 40kΩ / 10Ω/ ±(10% of R + 2cts)
Others
Measurement of resistance of auxiliary stakes RH & RS (up to 40kΩ)
Ufk
Complies with SEV 3569
1P SELECTIVE GROUND
Range / Resolution / Accuracy
0.20 to 39.99Ω - 40 to 399.9Ω / 0.01 to 0.1Ω / ±(10% of R + 10cts) (ISel via clamp)
LOOP IMPEDANCE (Zs (L-PE0 AND Zi (L-N OR L-L) – 1P LIVE GROUND
Live Ground
Installation Voltage / Frequency
90 to 500 V / 15.8 to 17.5Hz - 45 to 65Hz
High-current mode with TRIP
Zs (L- PE) & Zi (L- N or L - L)
Range / Resolution / Accuracy
Max. test current: 7.5 A
(0.050) 0.100 to 0.5Ω / 0.001Ω/ ±(10% of R + 20cts) • 0.5Ω to 3.999Ω / 0.001Ω/ ±(5% of R + 20cts) 3.999 to 39.99Ω/ 0.01Ω / ±(5% of R + 2cts) • 39.99 to 399.99Ω / 0.1Ω/ ±(5% of R + 2cts)
NO TRIP mode (Zs (L – PE) 0nly)
Test current 6mA – 9mA – 12mA (as required) 0.20 to 0.99Ω / 0.01Ω / ±(15% of R + 10cts) 1.00 to 1.99Ω / 0.01Ω / ± (15% of R + 3cts) 2.00 to 39.99 / 0.01Ω / ± (10% of R + 3cts) 40.00 to 399.9Ω / 0.1Ω ± (5% of R + 2cts) 400 to 3999Ω / 1Ω ±(5% of R + 2cts)
Calculation of IK short circuit current (PFC (Zs), I Sc PSCC (Zi)
Fault current and short-circuit current: 0.1 to20kA
Integrated Fuse Table
Yes
Voltage drop V%(Zi)
-40% to +40%
Others
Measurement of the resistive and inductive components of Zs and Zi impedances
AC and type RCDs
Installation voltage / Frequency
90 to 500V / 15.8 to 17.5Hz and 45 to 65Hz
IΔn
10/30/100/500/650/1,000 (90V - 280V) or variable ramp and pulse test
N-trip test
At ½ IΔn – Duration 1000ms or 2000ms
Ramp mode
0.2 to 0.5 x IΔn(Uf) / 0.3 x IΔn to 1.06 IΔn increments of 3.3% x IΔn
Trip test: R:
Range / Resolution / Accuracy
0.2 to 0.5 x IΔn(Uf) / 0.5 x IΔn / 2 x IΔn(selective) / 5 x IΔn
Pulse: 0 to 500ms/0.1 and 1ms / 2ms, Ramp mode: 0 to 200 ms / 0.1 ms / 2 ms
B-Type RCDs
Installation Voltage / Frequency
90 to 275V / 15.8 to 17.5Hz and 45 to 65Hz
IΔn: ramp / pulse 2 x IΔn
pulse 4 x IΔn
10/30/100/500mA
10/30/100/500 mA with pulse 4 IΔn
Duration: 150 ms with 4 x IΔn or 300 ms with 2 x IΔn
Test in ramp mode
0.2 x IΔn to 2.2 x IΔn
Trip test: 2 x IΔn
4 x IΔn
IΔn ≤ 200 mA: 2.2 x 2 x IΔn
IΔn ≤ 200 mA: 1.1 x 2 x IΔn
IΔn ≤ 100 mA: 2.2 x 4 x IΔn
OTHER MEASUREMENTS
Current by Current Probe C177A
5.0mA t0 199.9A
Current by Current Probe MN77
(1mA*) 5.0mA to 19.99A
Voltage
0 to 550VAC/DC / DC and 158 to 500Hz
Frequency
10 to 500Hz
Phase rotation
20 to 500VAC
Active power
0 to 110kW single phase – 0 to 330kW three-phase
Simultaneous display of voltage and current waveforms
Harmonics
Voltage and Current / up to 50th order / THD-F / THD-R
GENERAL SPECIFICATIONS
Display
Large 5.7” backlit graphic color LCD 320 x 240 pixels
Storage/Communication
USB for data transfer to DataView software (included)
Power Supply
Rechargeable battery Lithium-Ion 10.8V, 5.8Ah
Battery Life
Up to 30 hours
Protection
IP 53 / IK04
Dimension / Weight
11 x 7.48 x 5.04” (280 x190 x 128mm); 4.85 lbs (2.2 kg)
EMC
IEC61326-1
Safety
IEC61010-1 – 600V CAT III – 300V CAT IV – IEC 61557